    PolluFlow® Flow Sensor

    • check_circleUltrasonic measurement with no moving parts
    • check_circleWide size range from DN15 to DN100
    • check_circleFlexible installation in any orientation
    • check_circleCost-effective reprocessing after calibration
    • check_circleSeamless integration with PolluTherm systems
    Overviewarrow_downward_altResourcesarrow_downward_alt

    Ultrasonic flow sensor with volume pulse output

    Sensus PolluFlow® Ultrasonic Flow Sensor with volume pulse output has been designed for use with the PolluTherm® F Integrator for measuring heating and cooling energy. The measurement principle is based on the state-of-the-art ultrasonic technology.

    Ultrasonic technology offers many benefits: no moving parts, low pressure loss, wide flow measurement range and sensitive to low flow, large metering dynamics, and insensitiveness to suspended particles.

    Features

    • External power supply (e.g. through the integrator)
    • Standard pulsed output for the integrator
    • Approval according MID Classe 2 with dynamic range 1:100 (qi:qp)
    • No moving parts in the measuring channel
    • Choice between horizontal, vertical and inclined installation
    • Ideally suited for e.g. “6 °C/12 °C” refrigeration systems with water as the medium
    • Very good long term stability approved by AGFW duration test
    • Extreme low energy consumption enabling a long lifetime
    • 90 °C / PN16 with calculator PolluTherm® F
    • 130 °C/PN16 with calculator PolluTherm® or PolluWatt Duo II

    Wide temperature range:

    • PN16: 5 to 90 °C (short-term 105 °C)
    • PN25: 5 to 130 °C (short-term 150 °C)

    Specifications

    • Approved in accordance with EN 1434 and MID in Class 2 with dynamic range 1:100 (qi:qp)
    • 1L or 10L pulsed output for calculator depending on sizes
    • Material for flow sensor brass (qp 6 … 10 m³/h), grey cast iron (qp  15 … 60 m³/h)
    • Temperature range from 5-130 °C (briefly: 150 °C)
    • Installation in any position possible
    • Cable length 2,4m as standard, longer cable possible on request
    • Protection IP54 for heating, IP65 for cooling